Welcome to the Horel Electrical official website, we are professional manufacturer of low-voltage electrical !

Zhejiang HOREL Electrical CO.,LTD.

Online Contact

LC3 contactor

Application

 LC3 star delta starter
QJX2 (LC3-D)series "delta" decompression starter, mainly used for AC 50Hz or 60Hz, rated insulation voltage of 660V, in AC-3 using the category rated working voltage of 380V control power to 80KW three-phase squirrel cage induction motor, for controlling the motor stator windings by the "star" to "triangle" of for access starting, running and stopping, equipped corresponding specifications of the thermal relay, enabling the motor overload and phase failure protection.

technical parameters

Model

Rated operating current
A(AC-3)

Three-phase motor capacitykW(AC-3)

Weightkg

220V

380V

415V

440V

QJX2-093

9

4

7.5

7.5

7.5

1.5

QJX2-123

12

5.5

10

10

10

1.5

QJX2-163(183)

16(18)

11

15

15

15

1.7

QJX2-253

25

11

18.5

22

22

1.8

QJX2-323

32

15

25

25

25

2.00

QJX2-403

40

18.5

33

37

37

4.36

QJX2-503

50

25

45

45

45

4.36

QJX2-633(653)

63(65)

30

55

59

59

4.36

QJX2-803

80

37

63

75

75

5.20

QJX2-953

95

45

80

80

80

5.20

Specifications
TEL : 0577-62786986
ADD : No119 Xinguang Road Industry Liushi Town Yueqing City
Zhejiang Province China
WEB : www.chinahorel.com
E-mail : alan@chinahorel.com

Scan QR Code View Mobile Site
COPYRIGHT © 2012-2016 ZHEJIANG HOREL ELECTRICAL CO.,LTD. All RIGHTS RESERVED. DESIGN BY VIEYE
LINKS: Non - woven bag making machine | AC Kilowatt hour Meter | Circuit Breaker