DRN 6KA 1P+N RCD

DRN 6KA 1P+N RCD

Application

Application

DRNL earth leakage circuit breaker elcb electric shock,overload,short circuit protection are mainly applied to the AC 50/60Hz circuit rated 240V and 32A or below. DRNL elcb electric shock,overload,short circuit protection have the electric leakAge(electric shock),overload,short circuit and so on protection functions. The over voltage protection functions.The over voltage protection function can also be provided upon requirements. DRNL earth leakage circuit breaker elcb electric shock,overload,short circuit protection are mainly used to protect the buiding illumination and power distrion system.

Technical Data

DRNL-32

Standards

AS/NZS 61009 - 1

Magnetic tripping characteristics

B,C

Residual tripping characteristics

AC

Rated current

6 - 32

Rated residual current

10mA, 30 mA

Calibration temperature

30℃

Rated voltage 1P

240V

Frequency

50/60

Maximum service voltage

264

Tripping Duration:

Instaneous<0.1s

Power supply

Line & Load

Selectivity class

3

Residual making and breaking capacity

2000A

Short circuit capacity

4500A 6000A

Isolation application (IEC 60947-2)

Yes

Insulation resistance (Mohm)

1,000

Insulation voltage (V)

500

Dielectric rigidity (V)

2,500

Vibration resistance

1.5g

Endurance (operations) electrical

>6,000

mechanical

>20,000

Protection degree outside

IP20

inside enclosure

IP40

Self extinguishing degree (UL 94)

V2

Tropicalisation (IEC 60068-2)

+55℃/95% RH

Operating temperature

-5/+55℃

Storage temperature

-25/+70℃

Terminal capacity (top & bottom) min / max

1-16mm

Terminal torque (top / bottom)

3

Busbar systems

No

Accessories

No

Dimensions (mm)

71(H)81(L)18(W)

Weight (g)

85

Features & Advantages:
◇Top and bottom line and load compatible newest design for ease of installation.
◇ Two pole safety feature allows switching of both Active and Neutral contacts.
Active contacts always connect earlier and break later;
◇ Single module is ideal to save valuable switchboard space.

Normal Operation Conditions

Ambient Air temperature:Ambient air temperature range from -5℃ ~+40℃ ,not exceeding 35℃ averagely in 24 hours.
Location:installation location can not exceed 2000 meters above sea level.
Air conditons:Relative humidity in the installation palce can not exceed 50% when the air reaches the highest temperature +40℃ ,the average minimum temperature when it is the wettest can not exceed 25℃ Relative humidity not exceeding 90%.
Installation conditions:Magnetic field outsid the installation place can not exceed 5 times of the site of terrestrial magnetism in all directions.Normally speaking,RCBO should be mounted vertically .If the operation handle puts through power source upward,there should be no notable impact and vibration in the installation place.
LeakAge protection function of RCBO is tested and adjusted by the manufacture,users can not open the products at random during usage.
After using RCBO for a certain time(normally one month) , test button should be pressed noce in a state of making the circuit to check whether the function of RCBO is normal and reliable(press test button once, the RCBO can break off noce) . If abnormal, it should be unloaded and sent to the manufacturer to repair.
RCBO can not be wetted or soaked by rain,snow or water during the course or transportation storage and usage.

Electrical Diagram & Installation:
1-1.jpg 
Overall & installation dimensions
1-2.jpg 

Specifications
TEL : 0577-62786986
ADD : No119 Xinguang Road Industry Liushi Town Yueqing City
Zhejiang Province China
WEB : www.chinahorel.com
E-mail : alan@chinahorel.com

Scan QR Code View Mobile Site
COPYRIGHT © 2012-2016 ZHEJIANG HOREL ELECTRICAL CO.,LTD. All RIGHTS RESERVED. DESIGN BY VIEYE
LINKS: Non - woven bag making machine | AC Kilowatt hour Meter | Circuit Breaker