DC Mini Circuit Breaker

The HL7 is a DC circuit breaker dedicated to multi string photovoltaic installations. This circuit breaker is designed to protect the cables located between each string of photovoltaic modules and the 

photovoltaic inverter against overloads and short circuits (see application diagram). Combined with a switch , the HL7 will be installed in a string PV protection enclosure at the end of each string of 

photovoltaic modules. It can be locked (by a padlocking device) in OFF position as a safety measure for removal of the PV inverter. Since a fault current can flow in the reverse direction to the operating current, the HL7 can detect and protect against any 

bidirectional current. To ensure the safety of the installation, it is necessary, depending on the various types of application, to combine the HL7

 with:  a residual current device at the AC end  a fault passage detector (insulation monitoring device) at the DC end 

 an earth protection circuit breaker at the DC end In all cases, fast action on site will be required to clear the fault (protection not ensured in the event of a double fault). HL7 is not polarity sensitive: (+) and (-) wires can inversed without any risk. The HL7 is: delivered with three inter-pole barrier to provide increased isolation distance between two adjacent connectors.

Specifications

Item

 DC MINI CIRCUIT BREAKER

Code

HL7-63

Pole

1P

2P

3P

4P

Voltage

250VDC

550VDC/800VDC

750VDC

1000VDC/1200VDC

Current

1A,3A,6A,10A,16A,20A,32A,40,50A,63A

ated impact volt Uimp (KV)

4

Run breaking capacity ICs(%lcu)

75%

Standard

IEC/EN60947

Trip type

thermal magnetic

Breaking Capacity

6KA,10KA

Characteristic Curve

B,C,D

Mechanical

Actual average value

20000

Standard value

8500

Electric

Actual average value

2500

Standard value

1500

Working Temperature

“-5°”to +70°

Relative humidity

≤95%

Pollution Level

3

Installation Environment

No obvious shock and vibration

Protection Degree

IP20

Electrical life

More than 8000times

Mechanical life

More than 2000times

Dimension(W)X(H)X(D)

18X80X71

36X80X71

54X80X71

72X80X71

Installation

35MM DIN RAIL

Accessory

YES

Installation Altitude

≤2000M

Weight(KG)

0.12

0.24

0.36

0.48

 

Technical data

Position contact indication - suitability for isolation according to IEC/EN 60947-2 standard. 

 The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on

 the downstream circuit in complete safety. Increased product service life thanks to fast closing independent of the speed of actuation of the toggle.

Pre-wired product: Input / Output on the same side. 

Rated service breaking capacity (Ics)

100 % of the Icu

Endurance (O-C)

Electrical

1,500 cycles (where L/R=2 ms)

Mechanical

20, 000 cycles



Mechanical

20, 000 cycles

Degree of pollution

2

Category

A (no delay in accordance with IEC / EN 60947-2 standards)

Degree of protection (IEC 60529)

IP40

Tropicalisation

Relative humidity: 95 % at 55°C in accordance with IEC 60068-2 and GB 14048.2 standards

Temperature

Operating

-25°C to 70 °C

Storage

-40°C to 85°C

 

TEL : 0577-62786986
ADD : No119 Xinguang Road Industry Liushi Town Yueqing City